Testing Requirements and Precautions for Transformers Using FIW Winding as per IEC 62368-1
With the continuous development of electronic technology, insulated transformers are gradually moving towards miniaturization, lightweight, and high power density. Compared with traditional Triple Insulated Wire (TIW) and film-covered insulated wire, Fully Insulated Winding Wire (FIW) has the advantage of smaller size. Meanwhile, FIW has better winding performance and soldering performance than TIW, thus showing a trend to replace triple insulated wire and become the first choice for the new generation of insulated transformers. However, the adoption of FIW also means facing stricter international safety standards. In this regard, the third edition of IEC 62368-1 (2018) newly adds the usage conditions and testing requirements for transformers with FIW, as follows:
The FIW used in transformers shall comply with the certifications of IEC 60851-5:2008, IEC 60317-0-7, and IEC 60317-56.
In the transformer structure, the basic insulation, double insulation, or reinforced insulation between windings shall meet the dielectric strength test voltage required by Table G.4. Meanwhile, if mechanical separation is provided between windings, the electrical clearance and creepage distance between windings may not need to be considered.
Transformers shall be evaluated through thermal cycling tests:
a) Three transformer samples shall undergo 10 cycles of the following temperature cycles:
ⅰ. 68 hours at a temperature 10K higher than the maximum winding temperature measured under normal operation, with a deviation of ±2℃, but not lower than 85℃;
ⅱ. 1 hour at 25℃ ±2℃;
ⅲ. 2 hours at 0℃ ±2℃;
ⅳ. 1 hour at 25℃ ±2℃.
During each temperature cycle test, twice the working voltage shall be applied between the transformer windings.
b) After the thermal cycling treatment for the three samples:
Two of them shall be further evaluated through a damp heat test (48 hours), and then the dielectric strength test shall be conducted;
The other one shall be subjected to the dielectric strength test (with the voltage value referred to Table G.4) immediately at the end of the highest temperature in the last cycle of the thermal cycling test.
c) No insulation breakdown shall occur during the above tests.If the peak voltage Ut of the FIW across insulation is greater than 750V, a partial discharge test shall be conducted:
ⅰ. At room temperature, carry out the partial discharge test on the two samples that have undergone the thermal cycling test and damp heat treatment. Apply the measured repetitive peak voltage Ut to the transformer for the partial discharge test, with t1 being 5s and t2 being 15s;
ⅱ. The partial discharge at t2 shall be less than or equal to 10pC.
Precautions:
FIW is only applicable to Overvoltage Category (OVC) I or OVC II power systems (equipment), and cannot be used for OVC III or OVC IV.
FIW shall be incorporated into the U.S. insulation system, such as UL OBJY2, and the FIW insulation system shall comply with relevant requirements.
The FIW grade (Grade 3 to Grade 9) and wire diameter shall be matched with the withstand voltage requirements and selected according to Table G.5.
BTL currently has the testing capability of Appendix G.5.3.4 of IEC 62368-1, can provide complete testing services for manufacturers, issue test reports with relevant qualification recognition, and provide customers with more efficient one-stop services.
Relevant information
EU Releases Exemption Guidelines on Removability and Replaceability of Portable and LMT Batteries — Multiple Product Categories Relief Granted
On July 14, 2026, the European Commission published the "Commission Guidelines to Facilitate the Harmonised Application of Provisions on the Removability and Replaceability of Portable and Light Means of Transport (LMT) Batteries" (Commission Notice C(2026) 5032 final). These guidelines aim to provide a uniform interpretative framework for the implementation of Article 11 of the EU Battery Regulat
6G Developments: Past, Present and Future
The formulation of 6G standards has entered a more concrete phase. At the 3GPP RAN Plenary Meeting held in Singapore in June 2026, the industry made progress in multiple key research areas and finalized the timeline for Release 21, which is regarded as the first standard version expected to formally define 6G.
Overview of EN IEC 61000-4-29:2026
The key focus of the 2026 edition is to address new DC power distribution environments, especially higher-voltage DC systems. It also clarifies test generator capability, duration tolerance, current limitation during short interruptions, inrush current verification, result evaluation, and test report requirements. For products using 24 Vdc, 48 Vdc, 380 Vdc, 400 Vdc, 800 Vdc, or other DC input pow